SECTION 6 - JLG CONTROL SYSTEM

3121607

– JLG Lift –

6-19

l/S JOY. CENTER TAP BAD

Resistive joysticks: These faults occur when center tap voltage is not between
3.08 volts and 3.83 volts. Due to resistor tolerances there is a +/-.1 volt range
around these values where the fault may be indicated.
Inductive joysticks: These faults occur when center tap voltage is not between
2.18 volts and 2.70 volts. Due to resistor tolerances there is a +/-.1 volt range
around these values where the fault may be indicated.

PUMP SWITCHES LOCKED –
SELECTED BEFORE START
SWTICH

This fault occurs when a hydraulic function switch is closed before start switch is
closed.

FOOTSWITCH SELECTED BEFORE
START

User attempted to start machine with footswitch engaged.

2/4

Flash code 2/4 indicates steering digital inputs are faulty.
NOT REQUIRED

2/5

Flash code 2/5 indicates a function is prevented due to a cutout.

4

BOOM PREVENTED – DRIVE
SELECTED

A boom function is selected while a drive function is selected and drive cutout is
configured to prevent simultaneous drive & boom operation.

DRIVE PREVENTED – ABOVE

ELEVATION

Drive is selected while above elevation and drive cutout is configured to pre-
vent drive.

DRIVE PREVENTED – BOOM
SELECTED

Drive is selected while a boom function is selected and drive cutout is config-
ured to prevent simultaneous drive & boom operation.

DRIVE PREVENTED – TILTED &
ABOVE ELEVATION

Drive is selected while tilted and above elevation and tilt is configured to cutout
drive.

MODEL CHANGED – HYDRAU-
LICS SUSPENDED – CYCLE EMS

User changed model number using the analyzer. User must cycle power before
hydraulics system will be active again.

11

2/7

Flash code 2/7 indicates accelerator input is faulty.
NOT REQUIRED

2/8

Flash code 2/8 indicates a problem with a hydraulic filter. Not reported during 2
second power-up.

5

RETURN FILTER BYPASSED

Hydraulic return filter clogged

CHARGE PUMP FILTER BYPASSED Charge pump filter clogged

3/1

Flash code 3/1 indicates a contactor did not close when energized.
NOT REQUIRED

3/2

Flash code 3/2 indicates a contactor did not open when energized.
NOT REQUIRED

3/3

Flash code 3/3 indicates a driver problem. All driver faults are detected in a simi-
lar manner. Open circuit faults are detected when analog feedback reads too
high and the output is commanded off. Short to ground is detected when ana-
log feedback reads low and the output is commanded on. Short to battery is
detected when analog feedback reads Vbat and the output is commanded off.
Not reported during 2 second power-up.

6

ALTERNATOR/ECM POWER
SHORT TO GROUND

HOUR METER SHORT TO
GROUND

HOUR METER SHORT TO

BATTERY

HORN SHORT TO GROUND

HORN OPEN CIRCUIT

Table 6-3. Help Fault Codes, Displayed Faults, and Descriptions