SECTION 8 - DIAGNOSTIC TROUBLE CODES

8-14

– JLG Lift –

3121222

423

LIFT UP AT CUTBACK -
POWER MODULE CURRENT
LIMIT

The lift up portion of the power module
has reached thermal limit.

• Check for jammed or obstructed arm stack or pivot bushing.
• Check for excessively high current consumption in the pump,

ANALYZER -> DIAGNOSTICS -> PUMP -> PUMP CUR over 130
Amps with an empty deck.

• Refer to Pump Motor Electrical Evaluation in Section 4.8.

4-4 Battery Supply

DTC

FAULT MESSAGE

DESCRIPTION

CHECK

441

BATTERY VOLTAGE TOO
LOW - SYSTEM SHUTDOWN

The power module momentarily mea-
sured battery voltage under 14.5V
between ground board J1-39 and ground
board J1-40.

• Recharge batteries or check for damaged batteries.
• Check battery charger function.

442

BATTERY VOLTAGE TOO
HIGH - SYSTEM SHUTDOWN

The power module momentarily mea-
sured battery voltage > 37.0V.

• May be due to improper battery charging or incorrect voltage bat-

teries being used.

443

LSS BATTERY VOLTAGE
TOO HIGH

The load sensing system module
momentarily measured battery voltage >
34.0V.

• May be due to improper battery charging or incorrect voltage bat-

teries being used.

• Refer to Section 2.3: Troubleshooting in the LSS manual,

3124288.

444

LSS BATTERY VOLTAGE
TOO LOW

The load sensing system module
momentarily measured battery voltage <
9V.

• Recharge batteries or check for damaged batteries.
• Refer to Section 2.3: Troubleshooting in the LSS manual,

3124288.

446 LOGIC SUPPLY VOLTAGE

OUT OF RANGE

The system module logic supply voltage
was measured to be out of normal operat-
ing range by the interface PCB (<11V).

• This may be caused by a loose battery terminal, severely dis-

charged batteries, damaged battery, or an improper wire harness
connection.

• Drive, Steer, and Lift Prevented
• ZAPI - HEALTH (Status LED) - ON

4421 LOGIC SUPPLY VOLTAGE

OUT OF RANGE

The system module logic supply voltage
was measured by the power PCB to be
more than 34V for 10uS.

• This may be caused by a loose battery terminal, severely dis-

charged batteries, damaged battery, or an improper wire harness
connection.

• Drive, Steer, and Lift Prevented
• ZAPI - HEALTH (Status LED) - ON

4422 LOGIC SUPPLY VOLTAGE

OUT OF RANGE

The system module logic supply voltage
was measured by the power PCB to be
less than 11V for 10uS.

• This may be caused by a loose battery terminal, severely dis-

charged batteries, damaged battery, or an improper wire harness
connection.

• Drive, Steer, and Lift Prevented
• ZAPI - HEALTH (Status LED) - ON

6-6 Communication

DTC

FAULT MESSAGE

DESCRIPTION

CHECK

661

CANBUS FAILURE - POWER
MODULE

The control system failed to receive mes-
sages from the power module.

• Check for 24V between power module 12 position connector ter-

minal 1 and the power module B- terminal. If this is the problem,
the line contactor may be cycling on and off, making a clicking
noise when the machine is powered.

• Disconnect ground board J1 and power module connector.

Ground board socket J1-31 to power module connector socket
10 should have continuity. Ground board socket J1-32 to power
module connector socket 11 should have continuity.

• Turn on machine in platform mode. If DTC 662 is present, trouble-

shoot that DTC before continuing.

4-2 Thermal Limit (SOA)

DTC

FAULT MESSAGE

DESCRIPTION

CHECK