1 loading the ramp function generator, 5function blocks – Lenze E94A User Manual
Page 505

Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
505
5
Function blocks
5.133
L_SdRampGenerator - ramp function generator - S-ramp
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter
5.133.1
Loading the ramp function generator
By setting bLoadStartValue to TRUE the ramp function generator is loaded with the signal at
dnStartValue_n.
• This value is accepted immediately and output to nOut_n. No s-shape ramp-up or ramp-down
takes place.
• As long as bLoadStartValue = TRUE , the ramp function generator is inhibited.
Parameter
Possible settings
Information
C04340
0.001
s
1000.000 Acceleration / deceleration time
• Initialisation: 1.000 s
C04341
0.001
s
10.000 S-ramp time
• Initialisation: 0.100 s
C04342
As of library V02.02.xx.xx
-200.000
%
200.000 Setpoint at the input
• Display of the dnIn_n input signal.
C04343
As of library V02.02.xx.xx
-200.000
%
200.000 Setpoint at the output
• Display of the dnOut_n output si-
gnal.