Or winembeddedxp computer, External visu on a windows, Xp/xp embedded ipc (remote access) – Lenze PC-based Automation Industrial PC User Manual
Page 122

Industrial PC | Parameter setting & configuration
Visualisation with »VisiWinNET®«
Configuration of the OPC tunnel
122
L
2.5 EN - 01/2012
13.4.3
External visu on a Windows XP/XP Embedded IPC (remote access)
The »VisiWinNET®« application of the external Windows XP/XP Embedded IPC
accesses the OPC server of the control IPC (controller) (via OPC tunnel 1). In the
example, the IP address of the IPC (controller) is: 192.168.5.99
For configuring OPC tunnel 1, use the oct.xml configuration file in the
\Programs\Lenze\Lenze Digitec OPC Tunnel
directory. Enter the
corresponding IP address of the control IPC in the configuration file (as described in the
following section).
For configuring OPC tunnel 2, use the oct.xml configuration file. The standard
settings need not be changed.
Note!
For using an external Visu on a Windows XP/XP Embedded IPC, the oct.xml
configuration file on the Windows XP IPC must be adapted.