Clip-loc – Metal Sales Clip-Loc Installation User Manual

Page 20

Advertising
background image

© Metal Sales Manufacturing Corporation/ Subject to change without notice/ Effective Date 2/03

812.246.1935 (Corporate Offi ce) • www.mtlsales.us.com

19

CLIP-LOC

Panels must be field turned up at all high side conditions. Field bending panels up helps prevent moisture from draining into
building. It is recommended panels be installed, and then field bent. Do not cut panel.

1. Slide Clip-Loc Turn-Up Tool over panel end 2 inches.
2. Bend Clip-Loc panel up until fl ush with top of panel rib.
3. Repeat steps 1 and 2 for every panel.

D

ESIGN

/ I

NSTALLATION

C

ONSIDERATIONS

(

CONT

.)

PANEL HIGH SIDE TURN-UP

Field Bending Steps

FLASHING NOTCH

Clip-Loc flashings are available with factory turn-downs that will help conceal closures from weathering and help prevent mois-
ture drainage into building. Flashings must be field notched to fit over panel ribs. These types of flashings are available for
all high side conditions.

1. Place High Side Flashing on top of Clip-Loc panel ribs and mark center of each rib on fl ashing.
2. Slide notching tool over fl ashing leg and notch out for panel rib at every mark.
3. Repeat steps 1 and 2 for every panel rib.

Field Notching Steps

1

2

3

C

L

CL

C

L

C

L

C

L

1

2