Rockwell Automation PF700 PowerFlex 700 Drive Components Replacement - Frame 9 User Manual

Page 26

Advertising
background image

26

Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

Chapter 2 Basic Component Removal Procedures

3.

Remove the J1 and J2 connectors on the Precharge Board.

4. DC input only:

Remove the TB2 connector at the top of the Precharge

Board.

5.

Using your fingers or needle-nose pliers, squeeze the tabs of each of the
four spacers and remove the safety shield over the DC Bus Filter Board and
24V Power Supply Board.

6.

Disconnect the red and black wires from TB2 on the DC Bus Filter Board.

Do not

disconnect the wires from TB1.

7.

Disconnect the black Main Control Panel Thermal Sensor Wire above the
Main Control Board at the connector junction. See page

73

for its

location.

Do not

remove the sensor from the bracket.

8.

Carefully label and disconnect all wiring to TB9.

LT = Left and RT = Right

Power Interface Board

J6

J6

J8

J8

J16

U

U Phase CT

J15

V

V Phase CT

J14

W

W Phase CT

J23

UP, VP, WP

U, V, W positive gates

J18

UN, VN, WN

U, V, W negative gates

Connected Component

Wire Color

TB9 Terminal

Notes

Fan Harness

Black

120V, RT side

Lower 120V slot

Black

N, RT side

Upper N slot

Red

120V, LT side

Upper 120V slot

White

N, LT side

Upper N slot

Blower Harness

White

TB-9, RT side

White

TB-10, RT side

Connected Component

Label on Wire
or Connector

Label on Board

Notes

TB9 Shown with Factory Wiring only

Advertising
This manual is related to the following products: