Gate interface board, Remove components – Rockwell Automation PF700 PowerFlex 700 Drive Components Replacement - Frame 9 User Manual

Page 58

Advertising
background image

58

Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

Chapter 3 Component Replacement Procedures

8.

Install the Gate Interface Board:
a. Install the Gate Interface Board using the four nuts removed previously.

Torque screws to 2.9 N•m (26 lb•in).

b. Install the supplied Gate Interconnect Harness.
c. Connect wiring between the IGBT and Gate Interface Board as shown

in

Gate Interface Board on page 58

.

d. Connect wires to the Current Transducer.

9.

Install the three Snubber Capacitors in the reverse order of

Remove all

IGBT Snubber components: on page 29

.

Torque nuts to 5.6 N•m (50 lb•in).

10.

Reassemble remaining components in reverse order.

11.

Replace all safety shields and enclosure covers before applying power to the
drive.

Gate Interface Board

See

Chapter 1 - Drive Components

to locate the component detailed in these

instructions.

Remove Components

1.

Read and follow the

Safety Precautions on page 8

and

Important Initial

Steps on page 10

.

2.

Locate the Gate Interface Board to be replaced.

3.

Remove the safety cover over the Gate Interface Board.

4.

Label and disconnect all wires.

Connector

Wire Color(s)

Connects To:

J1

Red/White/Black

J1 on IGBT

J2

Red/White/Black

J2 on IGBT

J3

Red/White/Black

J3 on IGBT

J4

Orange/Black

J23 on Power Interface Board

J5

Blue/White

J18 on Power Interface Board

J6

Red/White

J4 on IGBT

J7

Red/White/Black

J7-W to J7-V (Gate Interface Boards W and V)
J7-V to J7-U (Gate Interface Boards V and U)
J7-U to J8 on Power Interface Board

J8

Black

J8-W to J8-V (Gate Interface Boards W and V)
J8-V to J8-U (Gate Interface Boards V and U)
J8-U to J6 on Power Interface Board

Advertising
This manual is related to the following products: