Dc link choke - ac input only, Remove components, Install components – Rockwell Automation PF700 PowerFlex 700 Drive Components Replacement - Frame 9 User Manual

Page 78

Advertising
background image

78

Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

Chapter 3 Component Replacement Procedures

DC Link Choke -
AC Input Only

See

Chapter 1 - Drive Components

to locate the component detailed in these

instructions.

Remove Components

1.

Read and follow the

Safety Precautions on page 8

and

Important Initial

Steps on page 10

.

2.

Locate the DC Link Choke.

3.

Label and disconnect DC Choke connectors (L1…L4).

4.

Label and disconnect wiring to TB15.

5.

Remove the four screws that mount the DC Link Choke to the DC Choke
Plate.

6.

Remove the DC Link Choke and properly discard.

Install Components

1.

Install new DC Link Choke to DC Choke Plate.

2.

Torque the four mounting screws to 9.0 N•m (80 lb•in).

3.

Reassemble remaining components in reverse order.

4.

Replace all safety shields and enclosure covers before applying power to the
drive.