Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

57

Component Replacement Procedures Chapter 3

4.

Reinstall the Transitional Busbar as instructed on page

32

.

5.

Install the three supplied negative (DC-) Flexible Capacitor Busbars in
positions 1, 3, and 5 on the IGBT.

The negative (DC-) Flexible Capacitor Busbars have a higher angle.

6.

Install the Tie Down Capacitor Mount:
a. Insert the short ends of the six threaded studs with nuts through the

Flexible Capacitor Busbars and into the left side of the IGBT. Torque to
5.6 N•m (50 lb•in).

b. Install the Tie Down Capacitor Mount with the two screws previously

removed from the top and bottom of the Capacitor Mount. Torque to
2.9 N•m (26 lb•in).

7.

Install the Current Transducer, AC Output Busbar, and Output Busbar
according to

Install Components on page 61

.

WARNING: Correct torque is critical to ensure correct operation
of the drive. Improper torquing could cause premature failure when
attempting to operate the drive.

Posi

ti

ve

(DC+) Fl

exi

ble Capacitor Busbars

Shown with Transitional Busbar and
all Flexible Capacitor Busbars installed

1

2

3

4

5

6

Negative (DC-) F

lex

ib

le Ca

pa

cit

or Bu

sb

ar

s