Converter snubber resistors - ac input only, Remove components – Rockwell Automation PF700 PowerFlex 700 Drive Components Replacement - Frame 9 User Manual

Page 64

Advertising
background image

64

Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

Chapter 3 Component Replacement Procedures

Converter Snubber
Resistors - AC Input Only

See

Chapter 1 - Drive Components

to locate the component detailed in these

instructions.

Remove Components

Kit includes Snubber Board and Resistor.

1.

Read and follow the

Safety Precautions on page 8

and

Important Initial

Steps on page 10

.

2.

Perform

Remove Main Control Panel on page 22

.

3.

Perform

Remove Stacking Panel on page 25

.

4.

Locate the Snubber Resistor(s) to be replaced.

5.

Verify the Snubber Resistor(s) with a volt ohm meter. The reading should
be 8 ohms ± 10%.
If the reading is not within tolerance, perform the remainder of this

procedure.

If the reading is within tolerance, do not perform the remainder of this

procedure.

6.

For the R Snubber Resistor only: Perform

Remove Transitional Busbar on

page 28

.

7.

Label and disconnect the wires from Snubber Resistor(s) that will be
replaced.

8.

Remove the resistor(s) and properly discard.

Snubber Resistor for “R” SCR

Snubber Resistor for “S” SCR

Snubber
Resistor for
“T” SCR

Advertising