Component Replacement Procedures Chapter 3

Install Components

1.

Place Fan assembly into the chassis but not installed in final position. Leave
space for accessing Fan cables from the front of the drive.

Take care to not pinch wires.

2.

From the front of the drive, reconnect Fan cables.

3.

Place Fan assembly in final position in the chassis.

4.

On the back of the drive, install the 11 screws for the Fan cover. Torque to
9.0 N•m (80 lb•in).

TIP

The connectors, one set shown below, are designed so they go
together only one way. The two end sections are flat on one side and
each section has a ridge at the matching edge.

Fan Cover Screw Locations on Back of Drive

4 on top and bottom
for a total of 8

3 on right side
NOTE: No screws on left side

Fan Assembly
(Front View),
Removed from Drive

Ridges

Flat Sections

Connectors shown
slightly separated