Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

9

Preface

Safety Precautions

The precautions and general installation requirements provided in the PowerFlex
700 Frame 7-10 Installation Instructions (publication

20B-IN014

) and the

PowerFlex 700 User Manual (publication

20B-UM002

) must be followed with

those included here.

1.

Turn off and lock out input power. Wait five minutes.

2.

Verify that there is no voltage at the drive’s input power terminals.

3.

Check the DC bus voltage at the Power Terminals by measuring between
the +DC and –DC terminals, between the +DC terminal and the chassis,
and between the –DC terminal and the chassis. The voltage must be zero
for all three measurements.

ATTENTION: To avoid an electric shock hazard, ensure that all
power has been removed before proceeding. In addition, before
servicing, verify that the voltage on the bus capacitors has
discharged. Check the DC bus voltage at the Power Terminals by
measuring between the +DC & -DC terminals, between the +DC
terminal and the chassis, and between the -DC terminal and the
chassis. The voltage must be zero for all three measurements.

Remove power before making or breaking cable connections. When
you remove or insert a cable connector with power applied, an
electrical arc may occur. An electrical arc can cause personal injury or
property damage by:

sending an erroneous signal to your system’s field devices,
causing unintended machine motion.

causing an explosion in a hazardous environment.

Electrical arcing causes excessive wear to contacts on the module and
its mating connector. Worn contacts may create electrical resistance.