Bus capacitor, Remove components – Rockwell Automation PF700 PowerFlex 700 Drive Components Replacement - Frame 9 User Manual

Page 49

Advertising
background image

Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

49

Component Replacement Procedures Chapter 3

Bus Capacitor

See

Chapter 1 - Drive Components

to locate the component detailed in these

instructions.

Remove Components

1.

Read and follow the

Safety Precautions on page 8

and

Important Initial

Steps on page 10

.

2.

Perform

Remove Main Control Panel on page 22

.

3.

Perform

Remove Stacking Panel on page 25

.

4.

Perform

Remove Transitional Busbar on page 28

.

5.

Label and remove all wires and connectors from the Bus Capacitor Busbar.

6.

Remove nuts and washers (18 each) fastening the Bus Capacitor Busbar to
the Bus Capacitors.

The setcrews may come out with the nuts. Save all nuts and setscrews.

7.

Remove the Bus Capacitor Busbar.

8.

Remove Capacitors by pulling them out; dispose of them properly.

Bus Capacitor Busbar

Transitional Busbar Unit
Removed

Bus Capacitor Busbar
Nuts and Washers (18 each)

Advertising