Install components – Rockwell Automation PF700 PowerFlex 700 Drive Components Replacement - Frame 9 User Manual

Page 32

Advertising
background image

32

Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

Chapter 2 Basic Component Removal Procedures

Install Components

See the photographs in the preceding

Transitional Busbar

section to identify any

components discussed in this section.

1.

Replace the three positive (DC+) Flexible Capacitor Busbars supplied in
an IGBT replacement kit on the back side of the Transitional Busbar for
each IGBT module being replaced.

2.

Mount Transitional Busbar to Bus Capacitors. If needed, use a rubber
mallet to gently tap the Transitional Busbar onto the longer setscrews of
the Bus Capacitors.

3.

Add a washer (rounded side down) and nut to each Bus Capacitor
setscrew. Finger tighten only.

4.

Install the nine negative Flexible Capacitor Busbars to the Transitional
Busbar with two washers (rounded side down) and two nuts for each
Flexible Capacitor Busbar. Finger tighten only.

5.

Install the six setscrews to secure the Flexible Capacitor Busbars to each
IGBT board. Finger tighten only.

IMPORTANT

Each IGBT replacement kit includes three positive (DC+) and three
negative (DC-) Flexible Capacitor Busbars. The positive ones are
shorter (see above) because they attach to the back side of the
Transitional Busbar. For ease of installation, replace positive Flexible
Capacitor Busbars while the Transitional Busbar is removed.

Negative (DC-)
Flexible Capacitor
Busbar (tall)

Positive (DC+)

Flexible Capacitor

Busbar (short)

Advertising