Rockwell Automation PF700 PowerFlex 700 Drive Components Replacement - Frame 9 User Manual

Page 41

Advertising
background image

Rockwell Automation Publication 20B-IN025B-EN-P - January 2011

41

Component Replacement Procedures Chapter 3

3.

Remove wiring to this Board, and wiring from this board to the Switch
Mode Power Supply Board.

Connector

Wire Color(s)

Connects To:

J1

Ribbon

J2 on Main Control Board (ribbon cable)

J2

Black

J1 on Switch Mode Power Supply Board

J6

Black

Monitor wire to thermal sensors

J8

Red/White/Black

J7-U on U Phase Gate Interface Board

J9

Red/White/Black

J1 on 24V Power Supply Board

J10

Red/Black/White/Blue

J3 on Precharge Board

J12

Red/White

J3 on Switch Mode Power Supply Board

J13

Black

J2 on Switch Mode Power Supply Board

J14

Red/White/Black

U Phase Current Transducer

J15

Red/White/Black

V Phase Current Transducer

J16

Red/White/Black

W Phase Current Transducer

J18

Blue/White

U, V, W negative (–) gates (lower phase)

J23

Orange/Black

U, V, W positive (+) gates (upper phase)

J24

Red/Black

J1 on Precharge Board,
TB1 on DC Bus Filter Board (AC input only)

TB1 on DC Bus Filter Board (DC input only)

TB1

Green/Yellow

PE on TB11

TB2

Red

#33, #34, and #35 on TB11

DC input shown

J1

J10

J8

J9

J16

J15
J14

J24

J13

J23

J18

TB2

J6

TB1

J2

Spacers (9)

J12

Advertising