Appendix B presents information about the WIM parameters.

The parameters in the WIM are numbered consecutively. You can use the
following configuration tools to access the parameters in the WIM.

Topic

Page

About Parameter Numbers

B-1

Parameter List

B-1

About Parameter Numbers

Configuration Tool

Numbering Scheme

• Pocket DriveExplorer for Pocket PC

• DriveExplorer

• DriveExecutive

• HIM

The adapter parameters begin with parameter
01. For example, Parameter 01 - [Adapter
Cfg]
is parameter 01 as indicated by this
manual.

Parameter List

No.

Name and Description

Details

01

[Adapter Cfg]
Sets the operating mode of the WIM.

Default:

0 = Auto

Values:

0 = Auto
1 = Master
2 = Slave
3 = RTU Master

Type:

Read/Write

Reset Required: Yes

02

[Adapter Type]
Displays the present operating mode of the WIM.

Default:

0 = Master

Value:

0 = Master
1 = Slave
2 = RTU Master

Type:

Read Only

03

[Drive Addr Cfg]
Sets the node address of the WIM for use with the WIM
operating mode set with Parameter 01 - [Adapter
Cfg]
. In Auto, Master or Slave mode, the WIM node
address can be any valid value. In RTU Master mode,
the WIM node address must match the address of any
drive on the network. Each network drive address, set
using drive parameter 104 - [Comm Node Addr], must
be unique.

Default:

1

Minimum:

1

Maximum:

247

Type:

Read/Write

Reset Required: Yes