Wireless Flash Updating DSI Peripherals

Figure C.19 Executing Flash Update Completed Screen

Click Close to exit the Flash Update Completed screen. The Device
Firmware Changed dialog box (

Figure C.20

) will appear.

Figure C.20 Device Firmware Changed Dialog Box

9. Depending on the device being flash updated, do one of the following:

–

When flashing a peripheral (not the WIM), click Yes.
DriveExplorer will re-establish the wireless connection to the
device. Then power cycle the drive to initialize the device with
the WIM.

–

When flashing the WIM, click No. The wireless connection to
the WIM breaks after the flash update, requiring a manual
reconnection. Use the Bluetooth Manager to re-establish the
wireless connection to the WIM. After wireless communication
is re-established, DriveExplorer will automatically reconnect to
the WIM.

10. With the DriveExplorer linear list screen (

Figure C.14

) displayed,

select the device (for this example, a 22-COMM-D communication
adapter). Then select Explore > Device Properties… to verify that
the Revision number shown on the General tab screen matches the
firmware version flashed into the device.