Wireless Flash Updating DSI Peripherals

Figure C.19 Executing Flash Update Completed Screen

Click Close to exit the Flash Update Completed screen. The Device
Firmware Changed dialog box (

Figure C.20

) will appear.

Figure C.20 Device Firmware Changed Dialog Box

9. Depending on the device being flash updated, do one of the following:

When flashing a peripheral (not the WIM), click Yes.
DriveExplorer will re-establish the wireless connection to the
device. Then power cycle the drive to initialize the device with
the WIM.

When flashing the WIM, click No. The wireless connection to
the WIM breaks after the flash update, requiring a manual
reconnection. Use the Bluetooth Manager to re-establish the
wireless connection to the WIM. After wireless communication
is re-established, DriveExplorer will automatically reconnect to
the WIM.

10. With the DriveExplorer linear list screen (

Figure C.14

) displayed,

select the device (for this example, a 22-COMM-D communication
adapter). Then select Explore > Device Properties… to verify that
the Revision number shown on the General tab screen matches the
firmware version flashed into the device.