Using RTU Master Mode

D-7

Figure D.7 Wiring Example for RTU Master Network

The AK-U0-RJ45-TB2P two-position terminal block connector
(

Figure D.8

) can be used to conveniently daisy-chain the PowerFlex

4-Class drives from Drive 1, which is connected to the WIM. Two
terminating resistors are also included with terminal block connectors in
the AK-U0-RJ45-TB2P kit.

Figure D.8 AK-U0-RJ45-TB2P Terminal Block Connector

Figure D.9

shows a wiring diagram for using the AK-U0-RJ45-TB2P

terminal block connectors.

Figure D.9 AK-U0-RJ45-TB2P Connector Wiring Diagram

Drive 1

(PowerFlex 4/40/400)

Drive 2

Drive 32

Up to 32 PowerFlex 4/40/400

Drives on RTU Master Network

AK-U0-RJ45-TB2P

Connector with

Terminating Resistor

AK-U0-RJ45-TB2P

Connector

RS-485

. . .

AK-U0-RJ45-SC1
Splitter Cable

AK-U0-RJ45-TB2P

Connector with

Terminating Resistor

HIM Bezel with

Installed WIM

Contains FCC ID: SNT-2XWIMNX

IC: 5450A-2XWIMNX

This device complies with Part 15 of the FCC rules.

Operation is subject to the following two conditions:

1) this device may not cause harmful interference, and

2) this device must accept any interference received,

including interference that may cause undesired operation

Pocket PC,

Laptop or

Desktop

Computer

Master Port

Slave Port

To Slave Port on

Splitter Cable

(connected to Drive 1)

To Drive 2

To Drive 32

120

Ω

¼ Watt

Resistor

120

Ω

¼ Watt

Resistor

. . .

. . .