3-2

Power Stack Frame Installation

1503E-IN001E-EN-P – June 2013

Description of Frame Options

Catalog Number

Part Number

1000V, 180 A, 3 phase, 50/60 Hz

1503E-FRZ1T

80187-547-51

1000V, 360 A, 3 phase, 50/60 Hz

1503E-FRZ1A

80187-547-52

2300V, 180 A, 3 phase, 50/60 Hz

1503E-FRAT

80187-547-53

2300V, 360 A, 3 phase, 50/60 Hz

1503E-FRAA

80187-547-54

3300V, 180 A, 3 phase, 50/60 Hz

1503E-FRCT

80187-547-55

3300V, 360 A, 3 phase, 50/60 Hz

1503E-FRCA

80187-547-56

4160V, 180 A, 3 phase, 50/60 Hz

1503E-FRET

80187-547-57

4160V, 360 A, 3 phase, 50/60 Hz

1503E-FREA

80187-547-58

Voltage ranges :

1000 = 800 to 1449 V

2300 = 1450 to 2499 V

3300/4160 = 2500 to 4799 V


Table 3.B – Power Stack Frame Specifications

Description

180 A

360 A

Input Voltages

(50/60 Hz)

1000 volts AC, 3 phase, +10% -15%
2300 volts AC, 3 phase, +10% -15%
3300 volts AC, 3 phase, +10% -15%
4160 volts AC, 3 phase, +10% -15%

Ambient Temperature

0°C to 40°C (32°F to 104°F)

Power Section

6 SCR at 1000 volts

12 SCR at 3300 volts

6 SCR at 2400 volts

12 SCR at 4160 volts

Repetitive Peak
Inverse Voltage Rating

1000 volts – 4500 PIV

3300 volts – 13000 PIV

2300 volts – 6500 PIV

4160 volts – 13000 PIV

Thermal Capacity

600% of FLA, 10 seconds (2 starts per hour, 5 minutes between starts)
450% of FLA, 30 seconds (2 starts per hour, 5 minutes between starts)

dv/dt Protection

R.C. Snubber Network

Maximum Heat
Dissipation (kW)

Start or Stop Cycle (@ 450% FLA)

Continuous

180 A

360 A

800 to 2499 V

7

13

.25

2500 to 4799 V

14

26

.25

Altitude

0 to 1000 m (0 to 3,300 ft)

(See Controller Deratings Table A-1 in Appendix A)

Net Weight
(Shipping)

1000 to 2300 V – 116 kg (255 lbs)

3300 to 4160 V – 125 kg (276 lbs)

Refer to Table 3.A for acceptable input voltage ranges.

For higher ambient conditions, contact Factory.



Specifications