Voltage sensing board dimensions, Mounting and connecting the voltage sensing board – Rockwell Automation MV SMC Flex OEM Components User Manual
Page 29
 
Power Stack Installation
4-13
1503E-IN001E-EN-P – June 2013
Voltage Sensing Board Dimensions
290.0 [11.42]
345.0 [13.5
8]
270.2 [10.64]
385.0 [15.1
6]
79.5
[3.13]
11.5 [0.45]
290.0 [11.42]
345.0 [13.5
8]
270.2 [10.64]
385.0 [15.1
6]
79.5
[3.13]
11.5 [0.45]
Figure 4.9 – Voltage Sensing Board Dimension Diagram
 
 
The voltage sensing board (VSB) should be mounted adjacent to the 
power stacks (refer to Figure 4.9 for dimensions). All connection 
points are to be made accessible. The same VSB is used regardless of 
the system voltage. 
Connect the voltage sensing board to the L1 to L3 and T1 to T3 
terminals of the power stack (refer to Chapter 7). Observe the 
connection points at the voltage sensing board per Table 4.E and 
Figure 4.10. 
Specifications for wire used on medium voltage connections: 
UL style 3239, #18AWG, 40 KVDC silicone rubber insulated wire. 
Table 4.E – Voltage Sensing Board Connections
System Voltage (V
LL
)
VSB Taps
800 – 1500
D
1501 – 2500
C
2501 – 4800
B
4801 – 7200
A
Mounting and Connecting