Bypass contactor control panel – Rockwell Automation MV SMC Flex OEM Components User Manual
Page 41
 
Vacuum Contactor Installation
6-3
1503E-IN001E-EN-P – June 2013
 
 
Four (4) clearance holes are provided in the control panel for 
mounting. The holes are 5.5 mm (0.219 in.) in diameter and are 
suitable for M6 (1/4-20) self-tapping fasteners. See Figure 6.2 for the 
control panel dimensions. 
1) Mount the control panel in a suitable location that is isolated from
medium voltage components. Be aware that the control plug wiring 
harness is 10 ft. (3 meters) in length. Ensure that the wiring harness 
route still allows for a proper connection to the contactor control 
plug. 
A T T E N T I O N
A T T E N T I O N
Do not mount the control panel in the same 
compartment as high voltage components. Low 
voltage components must be electrically isolated 
from high voltage components to ensure access 
is available when the unit is energized. Failure to 
do so may result in severe burns, injury or death. 
All dimensions in millimeters [inches]
Clearance holes (4)
5.5 mm [0.2 in.]
229 [9.00]
213 [8.38]
224
[8.83]
240
[9.46]
All dimensions in millimeters [inches]
Clearance holes (4)
5.5 mm [0.2 in.]
229 [9.00]
213 [8.38]
224
[8.83]
240
[9.46]
Figure 6.2 – Bypass Contactor Control Panel Dimensions
Bypass Contactor Control
Panel