Power Stack Installation

4-3

1503E-IN001E-EN-P – June 2013

Table 4.C – Power Stack Specifications

Description

180 A, 360 A, 600 A

Input Voltages 
(50/60 Hz)

1000 volts AC, 3 phase, +10%, -15%

2300 volts AC, 3 phase, +10%, -15%

3300 volts AC, 3 phase, +10%, -15%

4160 volts AC, 3 phase, +10%, -15%

6900 volts AC, 3 phase, +10%, -15%

Ambient
Temperature

0°C to 40°C (32°F to 104°F)

Power Section
(for 3 phases)

6 SCR at 1000/2300 volts

12 SCR at 4160 volts

12 SCR at 3300 volts

18 SCR at 6900 volts

Repetitive Peak
Inverse Voltage Rating

1000 volts – 4500 PIV

3300/4160 volts – 13000 PIV

2400 volts – 6500 PIV

6900 volts – 19500 PIV

Thermal Capacity

600% of FLA, 10 seconds
450% of FLA, 30 seconds

dv/dt Protection

R.C. Snubber Network

Maximum Heat
Dissipation (kW)

Start or Stop Cycle (@ 450% FLA)

Continuous

180 A

360 A

600 A

0 to 2499 V

7

13

22

.25

2401 to 4799 V

14

26

44

.25

4800 to 7200 V

21

39

66

.25

Altitude

0 to 1000 m (0 to 3,300 ft.)

(See Controller Deratings Table A-1 in Appendix A)

Net Shipping Weight
(3 phases)

Rating

1000 / 2300 V

3300 / 4160 V

6900 V

180A / 360A

105 kg (231 lb)

113 kg (249 lb)

126 kg (278 lb)

600 A

132 kg (290 lb)

154 kg (339 lb)

170 kg (374 lb)

Refer to Table 4.A for acceptable input voltage ranges.

180 A and 360 A ratings only for 1000 V power stack

For other ambient ranges, refer to Factory.

Dimensions

Refer to Figures 4.2 through 4.7 for the dimensions of the power
stacks.

Specifications