Control Component Installation

5-3

1503E-IN001E-EN-P – June 2013


I M P O R T A N T

I M P O R T A N T

800-2499V – Two fiber optic transmitters per

phase are used.

2500-4799V – Four fiber optic transmitters

per phase are used.

4800-6900V – Six fiber optic transmitters per

phase are used.


Connect control power to the interface board. Use a grounded supply
source from 110 to 240 +10, -15% VAC, 50/60 Hz, 15 VA.

Connect 5A current transformer (CT) secondary signals to the interface
board, noting the required CT polarity. Three-phase CTs are required.

Connect the interface board module common (upper right) to a suitable
ground location in the control compartment, as required.


NOTES:

1. Only ground the module common connection if the power

system is solidly or resistively connected to ground. If the
power system is ungrounded, do not do so.

2. Ensure that Ground Instruction Tag (part number 80006-346-01)

is affixed to the ground connection to alert the final customer
of this requirement.

SMC Flex Control Module

1) Connect the ribbon cables (5) to the back of the SMC Flex control

module.

2) Align the ribbon cables (5) from the SMC Flex Control Module

with the connectors on the Interface Board. Push the ribbon
connectors into the mating connectors on the interface board.

3) Use the supplied screws to securely fasten the module to the board

mounting bracket.

4) Supply power to the SMC Flex control module and make the

required control connections.


Refer to User Manual, MV SMC Flex Motor Controller Bulletin
1503E, 1560E,1562E – Publication 1560E-UM051_-EN-P
for
detailed instructions on wiring and programming the unit.