Component deratings, Appendix – Rockwell Automation MV SMC Flex OEM Components User Manual

Page 53

Advertising
background image

Appendix

A

1503E-IN001E-EN-P – June 2013

Component Deratings



The components described in this publication may be applied in a wide
variety of situations. Some applications may require component
derating. For example, at altitudes above 1000 m (3300 ft.), the
maximum current and basic impulse level (BIL) are reduced as shown
in Table A.1.


Table A.1 – Component Derating Table

Altitude Rating

Reduce Max.

Continuous Current Rating

by :

Reduce B.I.L.

Withstand Rating

by:

180 A

360 A

600 A

0 to 1,000 m

(0 to 3,300 ft)

1,001 to 2,000 m

(3,301 to 6,600 ft)

10 A

10 A

15 A

6.0 kV

2,001 to 3,000 m

(6,601 to 9,900 ft)

20 A

20 A

30 A

12.0 kV

3,001 to 4,000 m

(9,901 to 13,200 ft)

30 A

30 A

45 A

18.0 kV

4,001 to 5,000 m

(13,201 to 16,500 ft)

40 A

40 A

60 A

24.0 kV