Current loop gate drive power assembly (clgd) – Rockwell Automation MV SMC Flex OEM Components User Manual
Page 31
 
Power Stack Installation
4-15
1503E-IN001E-EN-P – June 2013
The CLGD power assembly is provided as a loose component with the 
power stacks. It should be mounted adjacent to the power stacks in a 
manner that allows the secondary cable assembly to be correctly 
installed (see below). The CLGD power assembly requires a 110/120 
or 220/240 VAC (50/60 Hz), 50 VA, primary source of power. 
 
 
Use the supplied three-phase cable assembly to make the secondary 
connections. Route the cable through the CLGD board CTs, as shown 
in Figure 4.11. Refer to Chapter 7 for typical wiring diagram. 
Figure 4.11 – Installation of Cable through CLGD CTs
The supplied cable comes with a protective sheath that should also be 
installed. It protects the cable and enhances the system insulation 
level. 
NOTE: There are three individual cable loops (one for each
phase) connected in series. The cable length must be 6.4 
metres (21 feet). Do not cut the extra length from these 
cables, as they represent the load for the transformer in 
the above power assembly. If they are shortened, the 
loop current will be incorrect, and the CLGD boards 
may not function properly during stop maneuvers. 
Current Loop Gate Drive
Power Assembly (CLGD)