Rockwell Automation MV SMC Flex OEM Components User Manual
Page 15
 
Power Stack Frame Installation
3-7
1503E-IN001E-EN-P – June 2013
A T T E N T I O N
A T T E N T I O N
It is the responsibility of the OEM to ensure that 
the final enclosure is suitably bonded to ground, 
and that provisions for grounding are made 
according to local electrical codes and 
standards. 
 
 
The CLGD power assembly is mounted on the front bottom of the 
frame (refer to Figure 3.4). All secondary connections are pre-wired 
for the power stack frame. It requires a 110/120 or 220/240 VAC 
(50/60 Hz), 50 VA, primary source of power. Refer to Chapter 7 for 
typical wiring diagrams. 
NOTE: There are three individual cable loops (one for each
phase) connected in series. The cable length must be 6.4 
metres (21 feet). Do not cut the extra length from these 
cables, as they represent the load for the transformer in 
the above power assembly. If they are shortened, the 
loop current will be incorrect, and the CLGD boards 
may not function properly during stop maneuvers. 
Grounding
Current Loop Gate
Drive Power Assembly
(CLGD)