Final test procedures, Chapter – Rockwell Automation MV SMC Flex OEM Components User Manual
Page 49
 
Chapter
8
1503E-IN001E-EN-P – June 2013
Final Test Procedures
Final Test Procedures
• Verify that the enclosure is properly grounded.
•
Verify that phase-to-phase and phase-to-ground clearances meet 
the requirements of the local electrical code. 
•
Visually check for sufficient electrical clearances, creepage 
allowances and bend radii. Refer to the applicable local electrical 
codes. 
•
Check the tightness of all power and control connections. Refer to 
Table 8.A for recommended torque values. Gently tug on all wires 
to ensure that they are properly connected. 
Table 8.A – Recommended Torque Values
Hardware
Recommended Torque
1/4 in.
6 ft·lb (8 N·m)
5/16 in.
11 ft·lb (15 N·m)
3/8 in.
20 ft·lb (27 N·m)
1/2 in.
48 ft·lb (65 N·m)
Control Wire Terminals
3 in·lb (0.3 N·m)
CLGD Power Assembly Terminals
50 in·lb (5.6 N·m)
SMC Flex Control Module Terminals
5 in·lb (0.6 N·m)
 
 
A T T E N T I O N
A T T E N T I O N
All hardware for electrical connections must be 
torqued to the above specifications. Failure to do 
so may result in electrical faults causing 
personal injury or damage to the equipment. 
• Check for cross-threaded hardware. In addition to the regular
power connections, check the connections and wiring to the 
voltage sensing board. 
• The high voltage silicone-insulated wires must be identified with
tube markers. Avoid routing the wires over any components. If the 
wires are routed across two heatsinks, there must be enough slack 
in the wire to allow at least 10 centimeters (four inches) of creepage 
between the heatsinks. Tie wraps must not tightly squeeze the high 
voltage wires, and must not be put on with a tie-wrap gun.