Additional tests, Spare parts – Rockwell Automation MV SMC Flex OEM Components User Manual

Page 52

Advertising
background image

8-4

Final Test Procedures

1503E-IN001E-EN-P – June 2013


Snubber

terminal

Temperature signal
fiber-optic transmitter

Current loop CT

Plug-in test

power supply

Gate signal

fibre-optic receiver

Cathode

terminal

Common
test point

+20V test point

Overvoltage
sense terminal

+5V test point

Yellow LED

Thermistor
connector

Gate signal
test point

J2

TP1

TP2

J6

RX1

TX1

TP3

TP4

J1

J4

J3

J5

Gate/Cathode
connector

Snubber

terminal

Temperature signal
fiber-optic transmitter

Current loop CT

Plug-in test

power supply

Gate signal

fibre-optic receiver

Cathode

terminal

Common
test point

+20V test point

Overvoltage
sense terminal

+5V test point

Yellow LED

Thermistor
connector

Gate signal
test point

J2

TP1

TP2

J6

RX1

TX1

TP3

TP4

J1

J4

J3

J5

Gate/Cathode
connector

Figure 8.2 –Current Loop Gate Driver (CLGD) Board Test Points

7. Check all line and load resistances to ground at the interface board.

The measurement for all voltages should be within 11 k ohms to 13
k ohms.

Additional Tests

Perform additional tests, as outlined in Chapter 3 of User Manual,
SMC Flex Motor Controller, Bulletin 1503E, 1560E, 1562E,
Publication 1560E-UM051_-EN-P.


Spare Parts

For a complete listing of spare parts, refer to User Manual, SMC Flex
Motor Controller, Bulletin 1503E, 1560E, 1562E, Publication
1560E-UM051_-EN-P.