Interpret the ok status indicator, Routing errors in dh-485 messaging, Routing errors in local dh-485 messaging – Rockwell Automation 1756-DH485 ControlLogix DH-485 Communication Module User Manual User Manual

Page 100

Advertising
background image

Publication 1756-UM532A-EN-P - May 2006

B-4 Troubleshoot the 1756-DH485 Module

Interpret the OK
Status Indicator

The three LED status indicators on the module provide information about
your module and the status of each channel. The following tables outline the
indicator condition and the corresponding status, and explain what each
condition means.

Interpreting the OK Status Indicator

Routing Errors in DH-485
Messaging

This section describes routing errors in local and remote messaging.

Routing Errors in Local DH-485 Messaging

If the 1756-DH485 module has a problem with routing a DH-485 message, it
may return a response with an error status of D0 hex. A PLC-5 controller
displays this error as D000 hex when monitoring the message instruction. If
you receive this error message, take the following actions:

• Check your message instruction to make sure a valid destination node

was entered.

• Check your default slot configuration to make sure that it matches the

location of the ControlLogix controller in the chassis.

• Make sure the 1756-DH485 module is turned on and verify chassis

power is recognized by the 1756-DH485 module.

If the Module OK
Indicator is

Module Status

Recommended Action

Off

Not operating.

Apply chassis power.

Verify module is completely inserted into
chassis and backplane.

Red, then Off

Performing self-test.

None, normal operation.

Green

Operating and routing
messages.

Verify module configuration.

Red

In major fault

Reboot module. If red reoccurs, then
replace module.