Publication 1756-UM532A-EN-P - May 2006

9-4 Communicate to a SLC 5/03 Controller on a DH-485 Network

Configure the Message

These are the configuration dialogs for the example message.

Data table memory is in the
SLC 5/03 controller. The
message is coming from the
ControlLogix controller.

Destination storage is in the
1756-L55 controller.

Path Item

Description

dhrio_ser_B

When you browse to
the local 1756-DHRIO
module appears if you
have it configured in
the I/O configuration
tree in RSLogix 5000
software.

2

Channel A of the
1756-DHRIO module.

10

The remote 1756-DHRIO is
node 12 octal or 10
decimal.

1

Backplane

14

1756-DH485 module in
slot 14.

2

Channel A of the
1756-DH485 module.

1

SLC 5/03 Controller Node
Address

TIP

You do not need to create a routing
table when your communication
method is CIP messaging.