Create the routing table in rslinx software, Create the routing table in rslinx software -9 – Rockwell Automation 1756-DH485 ControlLogix DH-485 Communication Module User Manual User Manual
Page 69
Publication 1756-UM532A-EN-P - May 2006
Communicate Between SLC Controllers over DH+ and DH485 Networks 6-9
Create the Routing Table in RSLinx Software
These are the routing tables needed for the example configuration.
In this example, the:
• SLC 5/03 controller is connected
to Channel A of the 1756-DH485
module. The 1756-DH485 node
address on the DH-485 network
is node 0.
• 1756-DHRIO and the
1756-DH485 modules are on the
same backplane.
• 1756-DH485 module is in slot 14.
• 1756-DHRIO module is in slot 8.
• Link ID of Channel B of the
1756-DHRIO is Link 20.
• SLC 5/04 controller is connected
to Channel B of the
1756-DHRIO.
• node address of the SLC 5/04
controller on DH+ is 10 octal or
8 decimal.
• SLC 5/03 controller initiates a
remote message to the SLC 5/04
controller.