Specifications

ControlLogix DH-485 Communications Module 1756-DH485

Attribute

Value

Module Location

ControlLogix chassis

Maximum Backplane
Current Load

850 mA @ +5.1V dc and 1.7mA @ 24V dc
from I/O chassis backplane

Power Dissipation

4.5 W

Thermal Dissipation, Max

15.4 BTU/hr

Isolation Voltage

50V

Tested to withstand 750V dc for 60 s

Available Communication Rates

19.2 Kbps (default) and 9600 Kbps

Wiring Category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, Industrial
Automation Wiring and Grounding Guidelines.

2 - on communications ports

Environmental Specifications

Attribute

Value

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0...60 °C (32...140 °F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):

-40...85 °C (-40...185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):

5...95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 10...500 Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Non-operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:

4 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10 V/m with 1 kHz sine-wave 80%AM from 80...2000 MHz

10 V/m with 200 Hz 50% Pulse 100% AM at 900 Mhz