Communicate from a Logix Controller to an SLC 5/03 Controller over EtherNet/IP and DH-485 Networks 10-5

This is the Communication tab for the remote message.

Path Item

Description

series_A

This means go to the
backplane to slot 5 where
the 1756-ENBT named
Series_A is located.
Series A is defined as
backplane 1, slot 5.

2

EtherNet/IP port.

100.100.100.7

The remote 1756-ENBT.

1

Go to the backplane of the
remote 1756 chassis.

14

Go to the slot location of
the 1756-DH485 module.

2

Go out Channel A of the
1756-DH485 module.

1

Go to Node 1 or the
location of the SLC 5/03
controller.

TIP

You do not need to create a routing
table when your communication
method is CIP messaging.