3-6 Use Data Highway 485 Network

This figure shows an example of remote DH-485 messaging between SLC/03
(or later) controller A and SLC 5/03 (or later) controller B. In this example, the
following information must be included in the remote DH-485 message
routing message instruction:

• Local DH-485 node = 020
• Destination link ID = 2
• Remote DH-485 node = 030

Remote DH-485 Messaging Between
SLC 5/03 Controller A and SLC 5/03 Controller B

Link IDs

To use remote DH-485 messaging, each network that is an originating network
or target network must have a unique link ID. The 1756-DH485 module
requires these link IDs to be decimal values between 1-199. Each DH-485
channel on a 1756-DH485 module must have its own unique link ID.

TE

RM

T T

A A A A

B B

ControlLogix Chassis

SLC 5/03 Controller A

Link ID 1

SLC 5/03 Controller B

Link ID 2

Channel A - Node: 020

Channel B - Node: 025

1756-DH485 Module

44053

AIC+

AIC

AIC+

AIC

Node: 030