Remote messaging, Remote upload and download, Remote messaging -7 – Rockwell Automation 1756-DH485 ControlLogix DH-485 Communication Module User Manual User Manual

Page 15: Remote upload and download -7

Advertising
background image

Publication 1756-UM532A-EN-P - May 2006

1756-DH485 Module Overview 1-7

Remote Messaging

The configuration of remote messaging is similar to data highway remote I/O
(DHRIO). It is achieved through routing table functions and module
configuration. The multi-hop functionality is available in RSLogix 5 and 500
(version 6.3 or later)

Remote Upload and Download

You can bridge EtherNet/IP and ControlNet networks to a DH-485 network
using the 1756-DH485 module

You can upload and download:

• all MicroLogix and SLC 500 controllers on DH-485 from NetLinx

network by using RSLinx Classic software.

• PanelView Standard terminals on DH-485 from NetLinx network by

using RSLinx Classic.

Logix controllers message via a NetLinx network through a ControlLogix
gateway to the DH-485 network to all MicroLogix and SLC 5/03 (and above)
controllers on DH-485 network. RSLinx Classic software on the DH-485
network can browse through the ControlLogix gateway to any device on a
NetLinx network.

IMPORTANT

Logix controllers on a NetLinx network will not be able to
initiate messages through the ControlLogix gateway to the
DH-485 network to fixed SLC 500, SLC 5/01, or SLC
5/02 controllers on a DH-485 network.