1756-DH485 Module Overview 1-9

Alphanumeric Indicators

When you apply power to the module, the alphanumeric display begins to
cycle through the following sequence.

1. All LEDs flash on then off -CHA, CHB OK

2. OK displays red then changes to green.

3. INIT displays.

4. Firmware Revision flashes on scrolling display: DH-485

5. Channel A and the network used for channel A.

6. Channel A node address.

7. Channel A status.

8. Channel B and the network used for channel.

9. Channel B node address.

10. Channel B status.

This sequence runs continuously during normal module operation.

Refer to Appendix B, Troubleshoot the 1756-DH485 Module and publication
1756-IN587, the ControlLogix DH-485 Communications Module Installation
Instructions, for more information about LEDs and status indicators.

EXAMPLE

For example, if your module uses the following:

• Channel A for DH-485 with node address 14
• Channel B is not connected

and the channels are operating properly, you see the
following sequence:

A DH, A#14, A OK, B DH, B#00, ONLY NODE