Troubleshoot the 1756-DH485 Module B-5

Routing Errors in Remote DH-485 Messaging

If the 1756-DH485 module has a problem with routing a Remote DH-485
Message, it may return a response with an error status of D0 hex. An SLC
controller displays this error as D000 hex when monitoring the message
instruction. If you receive this error message, take the following actions:

• Check your message instruction to make sure a valid local node

destination, link ID and destination node were entered.

• Check your routing table in each 1756-DH485 module that the message

passes through.

• Connect and apply power to all 1756-DH485 modules.

Interpret the Channel Status Indicators

If the Channel A
or B Indicator
is

In This Channel
Mode

Then the Channel
Status is

Take This Action

Off

All

Not online.

Place channel online.

DH485

No other node on the
network.

Check cables.

Green

DH485

Operating.

None, normal
operation.