Communicating with Your Module

Chapter 3

3-6

Controlling Heating and Cooling Elements

In applications where the control variable TPO of each loop is used for
both heating and cooling, the ladder logic for data single-transferred
to/from the 1771-TCM module must do the following:

Write the decimal value 35 (binary 00100011) to the high

byte of the output image word of the 1771ĆTCM module.

Read the low byte of the input image word of the

1771ĆTCM module.

If the low byte of the input image word of the 1771ĆTCM

module has the value 35

10

, move the value from the high

byte of the input image word of the 1771ĆTCM module to

the output image byte of the outputs driving the heating

elements.

If bit 0 (watchdog timer) of the low byte of the input

image word of the 1771ĆTCM module off, zero the output

image byte of the outputs driving the heating elements

and zero the output image byte of the outputs driving the

cooling elements.

If bit 0 (watchdog timer) of the low byte of the input

image word of the 1771ĆTCM module on and the low

byte of the input image word of the 1771ĆTCM module

does not have the value 35

10

or 37

10

, do not write to the

output image byte of the outputs driving the heating

elements.

High byte of 1771ĆTCM

output word

Low byte of 1771ĆTCM

input word

High byte of 1771ĆTCM

input word

HeatingĆelement outputs

HeatingĆelement outputs

35

10

?

35

10

00000000

2

Write the decimal value 37 (binary 00100101) to the high

byte of the output image word of the 1771ĆTCM module.

Read the low byte of the input image word of the

1771ĆTCM module.

If the low byte of the input image word of the 1771ĆTCM

module has the value 37

10

, move the value from the high

byte of the input image word of the 1771ĆTCM module to

the output image byte of the outputs driving the cooling

elements.

High byte of 1771ĆTCM

output word

Low byte of 1771ĆTCM

input word

High byte of 1771ĆTCM

input word

CoolingĆelement outputs

37

10

?

37

10

CoolingĆelement outputs

00000000

2

Write the decimal value 35 (binary 00100011) to the high

byte of the output image word of the 1771ĆTCM module.

High byte of 1771ĆTCM

output word

35

10

Loop back to step 2.

Step 2

Step 3

Step 4

Step 5

Step 6

Step 7

Step 8

Step 9

Step 10

Step 1

The key to this logic is the switching between reading the heat bits and
reading the cool bits from the same input image byte. The following figure
shows an example of PLC-5 ladder logic to handle data single-transferred
to/from the 1771-TCM module in an application where the control variable
TPO of each loop is used for both heating and cooling.