Calibration read block – Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual
Page 76
![background image](/manuals/579619/76/background.png)
Calibrating the Module
Chapter 8
8-3
The calibration read block contains 14 words as shown in Table 6.B.
Table 6.B
Calibration Read Block
Word Bits
Description
1
0-15
Block Identification Code Ċ 1100 0000 0000 0000 (C000
16
)
2
0
Bad Calibration Procedure
•
0 = OK
•
1 = Wrong calibration procedure was attempted with the calibration write block.
1
Calibration Hardware Failure
•
0 = OK
•
1 = Calibration cannot take place due to hardware failure.
2
Calibration Reference Out of Range
•
0 = OK
•
1 = Incorrect reference signal was used during calibration.
3-15
Reserved
3
0
LoopĆ1 Input Calibration Done
1
LoopĆ2 Input Calibration Done
2
LoopĆ3 Input Calibration Done
3
LoopĆ4 Input Calibration Done
4
LoopĆ5 Input Calibration Done
5
LoopĆ6 Input Calibration Done
6
LoopĆ7 Input Calibration Done
7
LoopĆ8 Input Calibration Done
8-15
Reserved
4
0-15
Reserved
Calibration Read Block