Chapter 4
Configuring the Module

4-5

Word

Description

Bits

13

0-15

Cool Minimum Cycle Time Ċ The minimum cycle time in seconds for which the cool bit is on. (0.00 thru 100.00)

14

0-15

Cool Maximum Cycle Time Ċ The maximum cycle time in seconds for which the cool bit is on. (0.00 thru 100.00)

15

0-15

Always = 0.

16

0-15

Always = 0.

17

0-15

Low Temperature Alarm Value Ċ A PV value at the low end of the sensor limit, but still above the minimum PV value

(0 thru 999.9



)

18

0-15

High Temperature Alarm Value Ċ A PV value at the high end of the sensor limit, but still below the max PV value (0 thru 999.9



)

19

0-15

Low Deviation Alarm Value Ċ An error value that specifies the greatest deviation below the set point that the process can tolerate.

(0 thru 999.9



)

20

0-15

High Deviation Alarm Value Ċ An error value that specifies the greatest deviation above the set point that the process can tolerate.

(0 thru 999.9)

21

0-15

Temperature Alarm Dead Band Ċ Once the temperature alarm bits are on, they are kept on until the temperature drops below the

high alarm by this value or rise above the low alarm by this value. The deadĆband value applies to all alarm values. (0 thru 100



)

22

0-15

Thermal Runaway Temperature Change Value Ċ This temperatureĆchange value divided by the period is the thermal runaway

rate. (0 thru 100



)

23

0-15

Thermal Runaway Period in Minutes Ċ The temperatureĆchange value divided by this period is the thermal runaway rate.

(0 thru 100)

Words 1 thru 23 of the loop-1 configuration block are identified by the

mnemonics L1C01 thru L1C23 in ProSet 700 software.

Words 1 thru 23 of the loop-2 configuration block are identified by the

mnemonics L2C01 thru L2C23 in ProSet 700 software.

Words 1 thru 23 of the loop-3 configuration block are identified by the

mnemonics L3C01 thru L3C23 in ProSet 700 software.

Words 1 thru 23 of the loop-4 configuration block are identified by the

mnemonics L4C01 thru L4C23 in ProSet 700 software.

Words 1 thru 23 of the loop-5 configuration block are identified by the

mnemonics L5C01 thru L5C23 in ProSet 700 software.

Words 1 thru 23 of the loop-6 configuration block are identified by the

mnemonics L6C01 thru L6C23 in ProSet 700 software.

Words 1 thru 23 of the loop-7 configuration block are identified by the

mnemonisc L7C01 thru L7C23 in ProSet 700 software.

Words 1 thru 23 of the loop-8 configuration block are identified by the

mnemonisc L8C01 thru L8C23 in ProSet 700 software.

To learn how to set gains for the PID loops of the temperature control
module, read chapter 5.