Preface - using this manual, Using this manual, Purpose of manual audience system compatibility – Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual

Page 6

Advertising
background image

Using this Manual

i

Using this Manual

This manual shows you how to use your Temperature Control Module (cat.
no. 1771-TCM) with an Allen-Bradley programmable controller and
Pro-Set

700 software for barrel temperature control applications. It

helps you install, program, calibrate, and troubleshoot your module.

You must be able to program and operate an Allen-Bradley programmable
controller to make efficient use of your barrel temperature control module.
In particular, you must know how to program block-transfer instructions.
If you do not, refer to the appropriate PLC

programming manual before

you attempt to generate a program for this module.

System compatibility involves data table use as well as compatibility with
I/O chassis, remote termination panels, and processors.

Data Table Use

Communication between the module and the processor is bi-directional.
The processor single-transfers output data through the output image table
to the module and single-transfers input data from the module through the
input image table. The module also requires an area in the data table to
store the block-transfer read and write data. I/O image table use is an
important factor in module placement and addressing selection. The
module’s data table use is listed in the following table.

Use of Data Table

Compatibility

Catalog

Number

Input

Image

Output

Image

ReadĆ

Block

WriteĆ

Block

Addressing

Chassis

be

Image

Bits

Image

Bits

Block

Words

Block

Words 1/2Ćslot

1Ćslot

2Ćslot

Chassis

1771ĆTCM

16

16

135

295 max

Yes

R

No

B

B = Compatible with 1771ĆA1B, A2B, A3B, A3B1, A4B, 1771ĆAM1, ĆAM2 chassis.

Yes = Compatible without restriction

R = Restricted compatibility; it cannot be in the same even/odd pair of slots with a 32Ćbit module

No = Not compatible

You can place your 1771-TCM module into any I/O module slot of the
I/O chassis. However, do not put the 1771-TCM module into the same
even/odd module-slot pair as a 32-bit-density module unless you are using
1/2-slot addressing.

Purpose of Manual

Audience

System Compatibility

Advertising