Specifications – Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual
Page 82

Appendix
A
A-1
Specifications
General Specifications
Number of PID Loops
8 individually isolated
I/O Chassis Location
any single I/O module slot
A/D Resolution
16 bits or 15 bits plus sign bit
Input Filtering
6Ćpole lowĆpass hardware filter
Calibration Interval
•
6 months for first interval
•
1 year for subsequent intervals
Isolation Voltage
Designed to withstand 1000V dc continuous between input
channels and between input and backplane connections.
Modules are 100% tested at 1200V dc for 1 second
between input channels and backplane connections.
Max Backplane Current Load
1.0A
Environmental Conditions
•
Operating Temperature
•
Rate of Change
•
Storage Temperature
•
Relative Humidity
•
0 to 60
o
C (32 to 140
o
F)
•
Ambient changes greater than 0.5
o
C/minute may
temporarily degrade performance during periods of
change.
•
-40 to 85
o
C (-40 to 185
o
F)
•
5 to 95% (without condensation)
Connecting Cable(s)
1771ĆNC6
= 1.8m (6 ft)
1771ĆNC15 = 4.6m (15 ft)
Keying
Between 26 and 28