Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual

Page 53

Advertising
background image

Chapter 7
Monitoring Status Data

7-3

Word Description

Bits

2

13

LoopĆ1 CV Ramp Rate Ċ (selected in bit 4 of word 3 of the configuration block)

0 = LoopĆ1 CV is not ramping.

1 = LoopĆ1 CV is ramping at the rate entered in word 4 of the configuration block.

14

LoopĆ1 Input High TC Range Alarm Ċ (based on thermocouple type set in bits 12-15 of word 2 of the configuration block)

0 = LoopĆ1 PV input is below the high TCĆrange alarm value.

1 = LoopĆ1 PV input is at or above the high TCĆrange alarm value.

15

LoopĆ1 Input Low TCĆRange Alarm Ċ (based on thermocouple type set in bits 12-15 of word 2 of the configuration block)

0 = LoopĆ1 PV input is above the low TCĆrange alarm value.

1 = LoopĆ1 PV input is at or below the low TCĆrange alarm value.

3

0-15

LoopĆ1 ConfigurationĆBlockĆError or GainsĆBlockĆError Word Ċ Indicates the first configurationĆblock or gainsĆblock word

containing an outĆofĆrange value or incompatible bit selection. (See appendix B for details on locating errors.)

0 = No error detected in configuration block or gains block for loop 1.

1 thru 23 in the leastĆsignificant pair of digits = configurationĆblock error Ċ (lowerĆdigits value = word containing error).

1 thru 57 in the upper pair of digits = gainsĆblock error Ċ (upperĆdigits value = word containing an outĆofĆrange value).

4

0-15

LoopĆ1 DynamicĆBlockĆError Word or AutoĆTuning Error Code Ċ Indicates the first dynamicĆblock word containing an

outĆofĆrange value or an autoĆtuning error. (See appendix B for details on locating errors.)

0 = No error detected in dynamic block or in autoĆtuning for loop 1.

1 thru 34 in leastĆsignificant pair of digits = dynamicĆblock error Ċ (lowerĆdigits value = word containing outĆofĆrange value).

65 thru 67 in the upper pair of digits = a code that indicates an autoĆtuning error.

Advertising