Chapter 6
Operating the Module

6-3

Word Description

Bits

6

0

LoopĆ2 Enable

0 = Loop 2 disabled.

1 = Loop 2 enabled if PID control mode selected (bits 7-8, word 2, config block).

1

LoopĆ2 Auto/Manual Mode Select

0 = Loop 2 is in the manual mode Ċ the manual output value (from word 9) is used as the CV value.

1 = Loop 2 is in the automatic mode Ċ the PID algorithm generates the CV value.

2

LoopĆ2 SetĆPoint Select

0 = Select the standbyĆtemperature setĆpoint value from word 7.

1 = Select the runĆtemperature setĆpoint value from word 8.

3

LoopĆ2 AutoĆTuning Enable

0 = Disable autoĆtuning.

1 = Enable autoĆtuning Ċ autoĆtuning can be invoked by an offĆtoĆon transition of bit 1 of word 34.

4

Always = 0.

5

LoopĆ2 PID Integral Term Reset Enable

0 = Accumulate PID integral term.

1 = Reset the PID integral term on the 0ĆtoĆ1 transition, and then allow accumulation until the next 0ĆtoĆ1 transition.

6-15

Always = 0.

7

0-15

LoopĆ2 Standby Temperature SetĆpoint Value Ċ Used when bit 2 of word 6 is off (0 thru 999.9



).

8

0-15

LoopĆ2 Run Temperature SetĆpoint Value Ċ Used when bit 2 of word 6 is on (0 thru 999.9



).

9

0-15

LoopĆ2 Manual Output Value (CV) Ċ Used when bit 1 of word 6 is off (-100.00 thru +100.00).

10

0

LoopĆ3 Enable

0 = Loop 3 disabled.

1 = Loop 2 enabled if PID control mode selected (bits 7-8, word 2, config block).

1

LoopĆ3 Auto/Manual Mode Select

0 = Loop 3 is in the manual mode Ċ the manual output value (from word 13) is used as the CV value.

1 = Loop 3 is in the automatic mode Ċ the PID algorithm generates the CV value.

2

LoopĆ3 SetĆPoint Select

0 = Select the standbyĆtemperature setĆpoint value from word 11.

1 = Select the runĆtemperature setĆpoint value from word 12.

3

LoopĆ3 AutoĆTuning Enable

0 = Disable autoĆtuning.

1 = Enable autoĆtuning Ċ autoĆtuning can be invoked by an offĆtoĆon transition of bit 1 of word 34.

4

Always = 0.

5

LoopĆ3 PID Integral Term Reset Enable

0 = Accumulate PID integral term.

1 = Reset the PID integral term on the 0ĆtoĆ1 transition, and then allow accumulation until the next 0ĆtoĆ1 transition.

6-15

Always = 0.

11

0-15

LoopĆ3 Standby Temperature SetĆpoint Value Ċ Used when bit 2 of word 10 is off (0 thru 999.9



).