Calibrating the Module
Chapter 8
8-2
The calibration write block contains 20 words as shown in Table 6.A.
Table 6.A
Calibration Write Block
Word Bits
Description
1
0-15
Block Identification Code Ċ 1100 1100 0000 0000 (CC00
16
)
2
0
Calibration High/Low
•
0 = Low
•
1 = High
1
Calibration Clock Ċ 1ĆtoĆ0 transition triggers calibration functions
2-15
Always = 0
3
0-7
Input Calibration Mask Ċ Bits 0 thru 7 respectively correspond to loops 1 thru 8 respectively.
8-15
Always = 0
4
0-15
Always = 0
5
0-15
Always = 0
6
0-15
Always = 0
7
0-15
Always = 0
8
0-15
Always = 0
9
0-15
Always = 0
10
0-15
Always = 0
11
0-15
Always = 0
12
0-15
Always = 0
13
0-15
Always = 0
14
0-15
Always = 0
15
0-15
Always = 0
16
0-15
Always = 0
17
0-15
Always = 0
18
0-15
Always = 0
19
0-15
Always = 0
20
0-15
Always = 0
Calibration Write Block