Fine tuning the loops, Block identification, Inferred decimal point – Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual

Page 40

Advertising
background image

Setting Gains

Chapter 5

5-2

After auto-tuning, you may want to fine-tune the loops. As you fine-tune a
loop, first try adjusting the proportional gain; this will have the greatest
impact. Your second choice for adjustment should be the integral gain.
The derivative gain should be the last choice for fine-tuning a loop.

If the loop has a problem over-shooting the set point, you may be able to
improve the loop response by doing one or more of the following (in order
of effectiveness):

1.

decrease the proportional gain

2.

decrease the integral gain

3.

increase the derivative gain

If the loop is slow in reaching the set point, you may be able to improve
the loop response by doing one or more of the following (in order of
effectiveness):

1.

increase the proportional gain

2.

increase the integral gain

3.

decrease the derivative gain

The first word of each gains block contains a block identification code (10
1000 1000 0000 1001 or 8809

16

) that you use to tell the module that it is a

gains block.

For each gain value, you enter a 16-bit integer value. However, as you
enter each gain value you must be aware of an inferred decimal point.

For

each

proportional gain, the inferred decimal point is 2 places from

the right (causing the resolution to be 0.01).

For

each

integral gain, the inferred decimal point is 4 places from the

right (causing the resolution to be 0.0001).

For

each

derivative gain, the inferred decimal point is 1 place from the

right (causing the resolution to be 0.1).

FineĆtuning the Loops

Set Point

Set Point

Block Identification

Inferred Decimal Point

Advertising