9

9-1

Troubleshooting

We describe how to troubleshoot your module by observing LED
indicators.

At power-up, the module turns the RUN/FLT indicator to red, then checks
for:

correct RAM operation
EPROM

operation

EEPROM

operation

After passing initial diagnostics, the module turns the RUN/FLT indicator
to flashing green. The indicator will continue to flash green until it receives
a valid block-transfer write. After the block-transfer write, it will stay
solid green during normal operation. It will turn red if it detects a fault
condition. If the RUN/FLT indicator is red, block-transfers will be
inhibited.

The lower CAL/COM indicator flashes green when the module is
communicating with the processor. The speed of the flashing is dependent
upon system speed.

Figure 7.1

Indicators

Indicator

When Green

When Red

RUN/FAULT

flashes Ċ during initial powerĆup

solid Ċ first valid blockĆtransfer write

successfully completed

solid Ċ a fault is

found

CAL/COM

flashes Ċ when communication is

taking place between the PLC processor

and the 1771ĆTCM module.

flashes Ċ during

calibration

Chapter Objective

Diagnostics Reported by

the Module