Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual

Page 92

Advertising
background image

Locationg Errors

Appendix B

B-2

The second word for each loop indicates dynamic-block and auto-tuning
errors for that loop.

Display of integer value in word 4,

7, 10, 13, 16, 19, 22, or 25 of the

status block

A nonĆzero value in

these two digits

indicate an error in the

autoĆtuning process

A nonĆzero value in

these two digits

indicate an error in the

dynamic block

Example: If a value 6724 is diplayed, the 67 in the upper

pair of digits would indicate an error in autoĆtuning and the 24

in the leastĆsignificant pair of digits would indicate an error in

the dynamic block

If This Word of

Status Block:

Contains This

Value:

The Error is:

4 (loop 1)

7 (loop 2)

xx00

No error detected in dynamic block.

7

(loop 2)

10 (loop 3)

13 (loop 4)

16 (loop 5)

19 (loop 6)

22 (loop 7)

25 (loop 8)

xx01

thru

xx34

A word in the dynamic block has an outĆofĆrange value

or incompatible bit selection. Locate the specific word

by the value in the 2 leastĆsignificant decimal digits of

the status word. (value = word)

Example: If the value in word 13 is xx17, word 17

(loopĆ4 manual output value) of the dynamic block

has an outĆofĆrange value,

00xx

No error in autoĆtuning the loop.

65xx

AutoĆtuning terminated because of thermal runaway.

66xx

AutoĆtuning terminated because the change in PV

(since initial PV temperature) has exceeded 200



.

67xx

AutoĆtuning terminated because PV is within 50



of

setĆpoint.