Monitoring Status Data

Chapter 7

7-22

Word Description

Bits

62

6

LoopĆ7 Low Deviation Alarm Ċ (set in word 19 of the configuration block)

0 = LoopĆ7 PV input is above the low deviation alarm value.

1 = LoopĆ7 PV input is at or below the low deviation alarm value.

7

LoopĆ8 Low Deviation Alarm Ċ (set in word 19 of the configuration block)

0 = LoopĆ8 PV input is above the low deviation alarm value.

1 = LoopĆ8 PV input is at or below the low deviation alarm value.

8

LoopĆ1 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ1 PV input is below the high deviation alarm value.

1 = LoopĆ1 PV input is at or above the high deviation alarm value.

9

LoopĆ2 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ2 PV input is below the high deviation alarm value.

1 = LoopĆ2 PV input is at or above the high deviation alarm value.

10

LoopĆ3 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ3 PV input is below the high deviation alarm value.

1 = LoopĆ3 PV input is at or above the high deviation alarm value.

11

LoopĆ4 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ4 PV input is below the high deviation alarm value.

1 = LoopĆ4 PV input is at or above the high deviation alarm value.

12

LoopĆ5 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ5 PV input is below the high deviation alarm value.

1 = LoopĆ5 PV input is at or above the high deviation alarm value.

13

LoopĆ6 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ6 PV input is below the high deviation alarm value.

1 = LoopĆ6 PV input is at or above the high deviation alarm value.

14

LoopĆ7 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ7 PV input is below the high deviation alarm value.

1 = LoopĆ7 PV input is at or above the high deviation alarm value.

15

LoopĆ8 High Deviation Alarm Ċ (set in word 20 of the configuration block)

0 = LoopĆ8 PV input is below the high deviation alarm value.

1 = LoopĆ8 PV input is at or above the high deviation alarm value.