Set the devicenet node address and data rate – Rockwell Automation 1788-EN2DNR EtherNet/IP to DeviceNet Linking Device User Manual User Manual

Page 11

Advertising
background image

Rockwell Automation Publication 1788-UM059A-EN-P - August 2014

11

Install the Linking Device

Chapter 2

2. Connect the power cable to the linking device.

The female terminal block connector is provided with the linking device.

3. Apply power to the linking device and DeviceNet network.

Set the DeviceNet Node
Address and Data Rate

Two methods can be used to set the DeviceNet node address and the data rate:

Use the node address and data rate rotary switches on the side of the

linking device

Use RSNetWorx for DeviceNet software

Set the DeviceNet Node Address and Data Rate by Using the
Rotary Switches

The rotary switches are on the right side of the linking device.

Set the desired node address and data rate according to the table below.

Pin No.

Description

1

+24 V DC

2

GND

3

PE (Protective Earth)

1 2 3

Switch

Node Address

00 - 63

DeviceNet node address

Other value

Node address selected via RSNetWorx
software

Switch

Data Rate

0

125 kbps

NA x10

NA x1

DATA RATE